2018 IEEE 1584 – 125 kVA Transformer Exception DELETED!

125 kVA – Going, going, gone!
After much speculation about the fate of the 125 kVA transformer “exception”, the 2018 Edition of IEEE 1584 – IEEE Guide for Performing Arc-Flash Hazard Calculations has finally been published and made it official.  The 125 kVA transformer exception has been deleted!

In its place is the new language:

“Sustainable arcs are possible but are less likely in three-phase systems operating at 240 V nominal or less with an available short circuit current below 2000A” Continue reading

IEEE 1584 – 125 kVA Transformer / Less than 240 Volts Exception

Download FREE Arc Flash Calculations

One sentence in the IEEE 1584 Standard, IEEE Guide for Performing Arc-Flash Hazard Calculations, frequently has people scratching their heads: Equipment below 240V need not be considered unless it involves at least one 125 kVA or larger low-impedance transformer in its immediate power supply. What does this sentence mean? What is so significant about 240 volts and 125 kilovolt-amperes?

Download:  125 kVA / 240 Volt Exception

 

 

 

About Jim Phillips: Electrical Power and Arc Flash Training Programs – For over 30 years, Jim Phillips has been helping tens of thousands of people around the world, understand electrical power system design, analysis, arc flash and electrical safety.

NFPA70E 2018 Update video by Jim PhillipsJim is Vice Chair of IEEE 1584, International Chairman of IEC TC78 Live Working and Steering Committee Member – IEEE/NFPA Arc Flash Collaborative Research Project. He has developed a reputation for being one of the best trainers in the electric power industry.  Learn More


Arc Flash & Electrical Power Training Classes
 by Jim Phillips Click Here

Arc Flash & Electrical Power Training Products by Jim Phillips Click Here

Sign-up for my monthly publication “Grey Matter” which contains news about new standards, conferences, technical articles, Electrical Engineering news and more! Click Here